D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 63
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
A# Exit Tone
Sounds an exit tone during exit delay at all keypads assigned to this area.
A# Exit Delay Time
Exit delay time for this area when Master Exit or Perimeter Exit arming.
For SIA CP-01 Compliance the Exit Delay Time must be between 45 sec and 255 sec.
A# Auto Watch
A# Verify Time
Use alarm verification with smoke detectors to reduce the number of false fire alarms. When
Verify Time is programmed, the control panel can check smoke detector point activations
before generating alarm signals.
Points are programmed individually to activate the verification feature. Refer to
Section 5.1 Point Index, page 130. Any resettable Fire point can activate alarm verification for
the area to which it is assigned. Use separate area alarm-verification relays.
To enable alarm verification on a point, program Point Index, Fire Point, Alarm Verify, and
Resettable as Yes.
Yes Point Restoral Report is not sent until the bell time expires or user
acknowledges alarm condition.
No Restoral Reports are sent when point restores, regardless of bell time.
Default: Yes
Selection: Yes or No
NOTICE!
You can turn off exit tones for individual keypads by programming the appropriate CC# 1 to 8
as No in CC# Exit Tone.
Default: 60 sec
Selection: 0 to 600 (in 5 sec increments)
NOTICE!
Points programmed for instant alarm response generate alarms immediately, even during exit
delay. To avoid instant alarms on points adjacent to the perimeter when leaving the area,
program P## Type as 3 (Interior Follower).
Default: No
Selection: Yes or No
Yes When the area is disarmed, Watch Mode turns on automatically.
No When the area is disarmed, Watch Mode must be turned on or off
manually.
NOTICE!
Controlled points must be programmed as P## Watch Point to generate a watch tone.
Default: 60
Selection: 10 to 60 (in 1-sec increments)
NOTICE!
– Do not enable the Cross Point feature in point indexes designated for Fire points.
– Check with your authority having jurisdiction (AHJ) to determine the maximum
verification time allowed.