64 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
When an Alarm Verification point senses an alarm, the control panel automatically removes
power to all Resettable points connected to the area’s Reset Sensors relay. The sensor reset
removes power to the sensors for the amount of time programmed in Verify Time. When
power is reapplied, a 60-sec confirmation window begins. If the detector is still in alarm or
experiences another alarm during the confirmation window, or a different Resettable
Verification point in the area senses an alarm, an alarm occurs.
Example: Verify Time is set for 20 sec. The alarm verification cycle starts when the detector
senses smoke or fire. No report occurs.
When the detector senses smoke or fire, the area’s sensor reset relay interrupts power to
points connected to it for the time in Verify Time.
When power restores to the points, the 60-sec confirmation window starts. If any detector,
reset during the verification time, experiences another alarm during the confirmation window,
an alarm occurs. If no activity occurs during this period, no alarm occurs and the verification
window ends. If a Verification point senses another alarm after the window ends, a new
verification cycle begins. Refer to Table 3.15 for an example of Verify Time.
Table 3.15 Verify Time
A# Duress Enable
Refer to Duress Type in Section 3.9 Miscellaneous, page 59 for an explanation of duress.
For SIA CP-01 Compliance:
A# Duress Enable must be set to Yes.
A# Area Type
Regular
Verification
Point
Activation
Verify Time/
Reset Sensors
60 sec
Confirmation
Restart Alarm Verification
Cycle if an Alarm
Verification point activates
Power removed,
ignore activity
Generate alarm if
additional activity
received
Example:
Total Cycle
time 80 sec
* 20 sec 60 sec
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set A# Verify Time to 60 sec.
Default: No
Selection: Yes or No
Yes Enable Duress alarm for this area
No Disable Duress alarm for this area
CAUTION!
The passcode you normally use for duress is not valid in an area with A# Duress Enable set to
No.
If a passcode with the appropriate L# Disarm authority is used to duress disarm an area with
A# Duress Enable set to No, NO AUTHORITY appears in the display. Also, if the keypad display
is moved to an area with A# Duress Enable set to No using [COMMAND][5][0], a valid duress
disarm passcode does not send a duress report.
Default: Regular
Selection: Regular, Master, Associate, Shared