80 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
CC# Enhanced Command Center
When a D1260 Series Keypad is installed at this keypad address, this item must be set to Yes.
Keypad Programming of CC# Enhanced Command Center
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the COMMAND CENTER option.
2. Press [ENT]. The CC NUM 1 – 16 option shows.
3. Enter the keypad number you wish to configure and press [ENT]. The keypad reads CC#
SCOPE, and then the current configuration (for example, PANEL WIDE).
4. Press [NEXT]. The current keypad type shows (for example, CC - 1 TYPE ENHANCED:
YES).
5. Press [ENT] to change the keypad’s type.
6. Press [NEXT] or [PREV] to toggle to No to indicate that the D1255 is not an enhanced
keypad, and then press [ENT] to save the changes.
When the keypad reads PARAMETER SAVED, your selection has been configured.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the Command Center option.
2. Press [ENTER]. The CC Num 1 – 16 option shows.
3. Enter the keypad number you wish to configure and press [ENTER]. The keypad reads
CC# Scope, and then the current configuration (for example, Panel Wide).
4. Press the Type softkey. The current keypad type shows (for example, CC (1) Type
Enhanced: Yes).
5. Press the Edit softkey to change the keypad’s type.
6. Press the Yes or No softkey, and then press the Save softkey to save the changes.
When the keypad reads Parameter Saved, your selection has been configured.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7212GV4), set CC# Supervised to Yes for the
fire annunciation keypad.
NOTICE!
Keypads that share the same address setting display the same text and emit the same tones,
regardless of which keypad’s keys are pressed.
Trouble SDI # Reports are always reported as Area 1, Account 1 Events regardless of the area
the SDI device is assigned.
NOTICE!
When this prompt is Yes, you cannot have duplicate DIP switch settings.
Default: No (Yes for Keypad 8)
Selection: Yes or No
Yes This keypad is a D1260 Series Keypad.
No This keypad is not a D1260 Series Keypad.