D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 95
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Perimeter Delay
Delay arms all Perimeter points in the area where the keypad is assigned. Entry and exit
delays are provided with this Arming function. This function does not cause a Perimeter
Instant point to act as a Delay point.
Watch Mode
This function informs you when a perimeter point or interior point that is programmed as P##
Watch Point is faulted while the area is disarmed. Interior points do not emit a Watch Tone if
the area is perimeter armed. This function provides keypad audible or visual and optional
relay activation (refer to A # Watch Mode in Section 3.14.1 Area Relays, page 118).
Perimeter Partial
Use this function to arm normal perimeter points and force-bypass faulted perimeter points,
regardless of their P## Bypassable setting. When these force-bypassed perimeter points
return to normal, they automatically return to service, even if P## FA Returnable is set to No.
Perimeter Partial arming has entry and exit delays.
View Area Stat
Use this function to view the armed status of all areas within the scope of the keypad
assigned to this area. The armed states include A# AREA # IS OFF (disarmed), A# AREA # IS
ON (master delay armed), ALL ON INSTANT (master instant armed), and AREA # PERIMETER
ON (perimeter instant armed or perimeter delay armed). All area types, master, associate,
regular, and shared can be viewed using this function.
Default: P
Selection: -, E, or P
Function No. Function Name Alternate Keystroke
5 Perimeter Delay Arm [COMMAND][3]
Default: E
Selection: -, E, or P
Function No. Function Name Alternate Keystroke
6 Watch Mode [COMMAND][6]
Default: P
Selection: -, E, or P
Function No. Function Name Alternate Keystroke
7 Perimeter Partial Arm [COMMAND][8]
NOTICE!
Perimeter Partial ignores the A# Force Arm/Bypass Max entry in Section 3.10 Area
Parameters, page 61.
NOTICE!
Local Only Reporting: No Closing Report is sent to the central station, but a Perimeter Delay
Closing Event is generated in the event log.
Default: P
Selection: -, E, or P
Function No. Function Name Alternate Keystroke
8 View Area Stat (Menu function only)