and then “ON” or cycling the thermostat will not reset a hard
lockout condition. Wait five seconds after turning on the main
power before pushing the RESET button when the DynaMax
Controller is in a manual reset condition. Wait for the status
LCD display to refresh indicating that the DynaMax
Controller is ready before releasing the reset button.
The DynaMax Controller will go into an automatic reset
condition, if the fault is not corrected, the boiler will stay in
the automatic reset state. Once the fault is corrected, the
boiler will automatically return to normal operating state.
5.4 ERROR TABLE
5.4.1 Manual Reset Codes
Table 16: Manual Reset Codes
Error
Int
#
Description
IGNIT_ERROR 1
To eliminate the hard lockout error,
1) Wait until the boiler has completed its post-purge
cycle, if applicable
2) Press and hold the ‘RESET” button until the display
reverts back to showing the supply temperature
3) Release the RESET button, the hard lockout has
been cleared
5.4.2 Automatic Reset Codes
Table 17: Automatic Reset Codes
Error Int # Description
E2PROM_READ_ERROR 0
Problems reading from
or writing to e2prom