12.19 IGNITION CYCLE
The ignition cycle is shown in the table below. The values are the default factory settings.
Table 44: DynaMax Ignition Cycle
State
Standby Pre Purge Safety ON Safety OFF
6
must be
detected
5
Note:
1. If a flame signal is detected at the end of the pre-spark period (Ignit_0) then a lockout will occur.
2. If at the end of the safety period (6 sec) no flame is detected the control will go to post-purge to remove the unburned gas.
After this a re-ignition attempt is started following the same cycle. The number of re-ignition attempts is limited to 2 after
which a lockout occurs.
3. The burner can only be on continuously for a period of 24 hours. After this the burner is switched off and a restart
sequence follows.
4. Sparking stops 2 seconds before the end of the Ignit_1 period to allow for ionisation detection when measuring ionisation
through the spark plug.
5. If after post_purge_0 time (max. 10 sec.) still flame is detected lockout follows
6. Safety ON/OFF in this state the correct working of the safety relay is proved.
If the ignition cycle is started it will continue until completion, even if the demand is removed.