EasyManua.ls Logo

Camus Hydronics DynaMax DMH081 - PART 10 TROUBLESHOOTING; Troubleshooting Table Overview

Camus Hydronics DynaMax DMH081
93 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
PART 10 TROUBLESHOOTING
Table 29: Troubleshooting Table
COMPONENT FAILURE MODE ANALYSIS
Incoming Power
• Two wires interchanged • No effect on safety
• Live and Neutral wires are interchanged.
Transformer
Tripped
• The 24Volts and 120 Volts
wired are interchanged
• Transformer immediately burns out, replace
transformer
• Fuse on DynaMax Controller blows, replace 3.15A
fuse located at F1 on DynaMax Controller.
Pump Fails to
Circulate
• Wiring Issue • Check that wires are correctly wired from the
DynaMax Controller to the pump delay relay.
• Check that 115V is delivered to pump coil.
• Faulty Pump on a wet rotor
pump
• Pump impeller may be stuck. Use a flat head
screwdriver on face of pump to turn impeller
manually
• Replace Pump
• Air in the piping system
• Purge all air from the piping system
• Internal Fault on DynaMax
Controller
• Replace DynaMax Controller
Relief Valve
• System pressure exceeds relief
valve setting
• Replace the standard relief valve with a higher rated
valve up to the maximum pressure of the heat
exchanger.
• Improperly sized expansion tank.
Flow Proving
Device/ LWCO
• Flow Proving Device/ LWCO
contacts are open
• Verify LED’s on current sensing transformer during a
heat demand (wall hung)
• Check flow switch paddle (floor mount)
• Verify for closed valves or obstructions in boiler
piping
• Verify that all air has been purged from the system
• Verify that wiring is correct
• Blown Fuse • Replace 3.15A Fuse located at F1 on DynaMax
Controller.
DO NOT use alternates as it may damage the
DynaMax Controller

Table of Contents

Related product manuals