Camus Hydronics DynaMax DMH081 - PART 9 DYNAMAX CONTROL PANEL (Continued); DHW Parameter Mode Details

Camus Hydronics DynaMax DMH081
93 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40
Display Display Readout Description
DHW_Store_Hyst_Up
(Mode 1)
Used to end a call for heat
(Default: 9
o
F)
DHW_Store_Hyst_Down
(Mode 1)
Used to start a call for heat
(Default: 4
o
F)
DHW_Store_Supply_Extra
(Mode 1)
Increases the target outlet
temperature
(Default: 20
o
F)
DHW_Supp_Hyst_Up
(Mode 1, 2)
Temperature above set point to stop
burner for DHW. This parameter is to
match DHW_store_hyst_up
(Default: 9
o
F)
DHW_Supp_Hyst_Down
(Mode 1, 2)
Temperature above set point to stop
burner for DHW. This parameter is to
match DHW_store_hyst_down
(Default: 9
o
F)
.
DHW_Hyst_up
(Mode 4)
To provide modulation rate above
the DHW_setpoint.
(Default: 9
0
F)
DHW_hyst_down
(Mode 4)
To provide modulation rate below the
DHW_setpoint.
(Default: 4
o
F)
Pre-Heat Setpoint
(Mode 1, 4)
During a DHW request, the user will
not be subjected to a stream of cold
water when the tap is first turned on.
This also creates a buffer zone for
the boiler to fire up and modulate.
(Default: 110
o
F)
Pre-Heat hyst_up
(Mode 1, 4)
To provide modulation rate above
Pre-heat setpoint for the plate heat
exchanger during pre-heat.
(Default: 0
o
F)
Pre-Heat hyst_down
(Mode 1, 4)
To provide modulation rate below
Pre-heat set point for the plate heat
exchanger during pre-heat.
(Default: 9
O
F)