EasyManua.ls Logo

Camus Hydronics DynaMax DMH081 - PART 10 TROUBLESHOOTING (Continued); Noisy Operation Diagnosis; High Limit Trip Troubleshooting; Fan Speed Issues

Camus Hydronics DynaMax DMH081
93 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
SYMPTOM FAILURE MODE ANALYSIS
Noisy Operation
• Supply Gas Issue
• Refer to Part 3 Gas Connection in this manual.
• Natural Gas Pressure should read between 3” w.c.
and 14” w.c.
• L.P. Gas Pressure should be at 11” w.c.
• Air/Gas Mixture Issue • Refer to Gas Valve Adjustment Procedure in section
10.2 of this manual for the proper combustion
setting.
• Air Inlet and/or Vent
configuration
• Refer to Part 2 Air Inlet and Venting
• Dirty/ Damaged burner • Refer to Burner Maintenance in section 11.7 of this
manual for the burner removal and inspection
procedure. Clean or replace the burner, if required.
• Air in the piping system
• Purge all air from the piping system
• Incorrect igniter gap
• Check that spark gap is 9/64”
Auto Reset High
Limit Trips
• The supply/ outlet temperature
has exceeded 210
o
F.
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the boiler is piped properly. Refer to
Piping Diagrams in Section 13 of this manual.
• Verify that 120VAC is being supplied to the boiler
pump on a call for heat. If voltage cannot be
detected check wiring.
• Verify that the pump is circulating when 120VAC is
detected. If not, pump impeller may be stuck. Use a
flat head screwdriver on face of pump to turn
impeller manually
• If 120VAC is present during a call for heat, but the
pump still does not circulate, replace the pump.
• Replace the main DynaMax Controller if necessary
Manual Reset
High Limit Trips
(Pressing the
manual RESET
on the DynaMax
Control Panel will
be required to
restart the ignition
sequence)
• Manual Reset Safety High Limit
tripped, supply/outlet
temperature in excess of 210
o
F
• Verify that the capillary tube is broken. If this is the
case, replace Manual Reset High Limit
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the boiler is piped properly. Refer to
Piping Diagrams in Section 13 of this manual.
• Verify that 120 VAC is being supplied to the boiler
pump on a call for heat. If voltage cannot be
detected check wiring.
• Verify that the pump is circulating when 120 VAC is
supplied. If so, pump impeller may be stuck. Use a
flat head screwdriver on face of pump to turn
impeller manually.
• If 120 VAC is present during a call for heat, but the
pump still does not circulate, replace pump.
Fan Speed Too
Low
• Actual fan RPM is 30% slower
than target fan speed.
• Verify wiring connections at the fan and DynaMax
Controller.
• Replace the fan
• Replace the DynaMax Controller.
Fan Speed Too
High
• Actual fan RPM is 30% faster
than what is required.
• Vent/ Air Inlet Lengths exceed the maximum allowed
equivalent lengths. Refer to Air Inlet and Venting
Section in Part 2 of this manual.
• Verify that there are no obstructions in the vent/ air
inlet pipes or at terminations
• Verify wiring connections at the fan and DynaMax
Controller.
• Replace the fan
• Replace the DynaMax Controller.

Table of Contents

Related product manuals