EasyManuals Logo

Capstone Microturbine C1000 Series User Manual

Capstone Microturbine C1000 Series
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
Capstone Turbine Corporation • 16640 Stagg Street • Van Nuys • CA 91406 • USA
Installation Guide: Capstone C1000S/C800S/C600S with C1000 Series Controller
480064 Rev C (December 2018) Page 50 of 122
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
5.4.2. Air Inlet
Airflow requirements for each model are listed in Table 10. Airflow requirements are the same for
all C1000S/C800S/C600S configurations, including low pressure and dual mode versions with
batteries.
Table 10. Air Flow Requirements at ISO Conditions with Zero Backpressure
Microturbine Model
Airflow Requirements
C600S
18,600 scfm (526,800 slpm)
C800S
24,800 scfm (702,400 slpm)
C1000S
31,000 scfm (878,000 slpm)
In the process of producing power, the internal components electronics, gas compressors, etc.
produce heat. This heat must be removed by the enclosure cooling air supply under all potential
operating conditions. Following the inlet air flow rate requirements in the C1000S Product
Specification (Table 1) will ensure successful internal cooling through the full range of ambient
conditions. Additional information regarding allowable pressure drops and their effect on
microturbine performance can be found in the C1000S/C800S/C600S Technical Reference
(Table 1).
CAUTION
Too much inlet pressure drop can result in engine damage when installed
indoors or within a third party enclosure. The maximum allowable inlet pressure
differential to the microturbine enclosure is 249 Pa (1 inch WC) with reference
to outdoor ambient pressure.
5.4.3. Enclosure/Electronics Exhaust
Enclosure/electronics exhaust can exit the microturbine enclosure at temperatures greater than
38 °C (100 °F). The microturbine must have enough ventilation to accommodate the heat rejection
levels shown in Table 11. Care should be taken around the enclosure exhaust, especially for
indoor installations. When installed outdoors, the microturbine enclosure exhaust is typically trivial
when proper installation guidelines are followed.
Table 11. Heat Rejection per Microturbine Model
Microturbine Model
Heat Rejection
C600S
135 kW (460,600 BTU/hr)
C800S
180 kW (614,200 BTU/hr)
C1000S
225 kW (767,700 BTU/hr)
5.4.4. Engine Exhaust
The engine exhaust system consists of a single pipe exiting the recuperator and vented through
the top of the enclosure. The exhaust ducting should be rated up to 371 °C (700 °F). Proper care
should be taken in the disposal of this heat, whether that disposal is in the form of heat recovery
or exhaust to the ambient air. The main objective is to transfer the hot exhaust to an acceptable
area with minimal pressure drop or flow restriction.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Capstone Microturbine C1000 Series and is the answer not in the manual?

Capstone Microturbine C1000 Series Specifications

General IconGeneral
BrandCapstone
ModelMicroturbine C1000 Series
CategoryController
LanguageEnglish