62-11785 5–24
ECONO MAX. TEMP OFF
-20°F to +119.0°F (-
28.9°C to
+48.4°C ) (in 0.5°
increments)
Default: 119.0°F (48.4°C)
OFF = There is no upper limit for this parameter.
Select the highest ambient temperature desired to
activate ProductShield Econo
If ProductShield Econo Install is Go To Continuous
there is a minimum 10°F range. Therefore, this
parameter’s lower limit is ProductShield Econo Min
Temp plus 10°F (5.5°C).
ECONO DELTA-T
NOTE: This is available for “Go
to S/S only. It is not available for
“Go to Continuous”.
OFF
+3.6°F to +27.0°F (+2°C to
15°C) (in 0.5° increments)
OFF = Delta-t is not used in determining when the
unit will go into Econo: Go To Start/Stop Mode.
Select the desired delta-t value for activation of
ProductShield Econo. When delta-t is below this
setting and within the minimum/maximum range go
to start/stop will be allowed.
PRODUCTSHIELD: WINTER OFF
-20°F to +32.0°F (-28.9°C
to 0°C) (in 0.5° C or °F
increments)
Select the desired ambient temperature below
which ProductShield Winter will operate (forced
Continuous Run operation).
ALARM SETTINGS
Configuration Selections Description
OUT OF RANGE SHUTDOWN YES / NO YES = When the refrigerated compartment
temperature has been out-of-range for 45 minutes,
the alarm light will come on, and the unit will shut
down.
NO = When the refrigerated compartment
temperature has been out-of-range for 30 minutes,
the alarm light will come on and the unit will
continue to run. Refer to Alarm 00053 BOX TEMP
OUT-OF-RANGE
LOW PRESSURE SHUTDOWN YES / NO YES = When alarm 00018 LOW REFRIGERANT
PRESSURE is activated the alarm light will
illuminate and the unit will shut down.
NO = When alarm 00018 LOW REFRIGERANT
PRESSURE is activated the alarm light will
illuminate and the unit will continue to run.
LP SHUTDOWN DELAY (0 - 10 seconds)
10 SECS
If the Low Pressure Shutdown Configuration is set
to YES, shutdown is to be delayed for this amount
of time after the Low Pressure Shutdown signal is
received.
HIGH SUCT PRESS
SHUTDOWN
YES / NO YES = When alarm 00027 HIGH SUCTION
PRESSURE is activated the alarm light will
illuminate and the unit will shut down.
NO = When alarm 00027 HIGH SUCTION
PRESSURE is activated the alarm light will
illuminate and the unit will continue to run.
Table 5–1 Configuration Settings
(Refer to Section 5.2.3 for instructions on entering Configuration settings)
Configuration Selections Description