5–25 62-11785
REFRIGERATION SYS
SHUTDOWN
YES / NO YES = When alarm 00028 CHECK
REFRIGERATION SYSTEM is activated the alarm
light will illuminate and the unit will shut down.
NO = When alarm 00028 CHECK
REFRIGERATION SYSTEM is activated the alarm
light will illuminate and the unit will continue to run.
COMPRESSOR ALARM
SHUTDOWN
YES / NO If the “Compressor Alarm Shutdown” option has
been installed (refer to Unit Data), this setting will
be available.
YES = The unit will shutdown and not restart when
00013 HIGH DISCHARGE PRESSURE, 00017
HIGH COMP DISCHARGE TEMP, 00018 LOW
REFRIGERANT PRESSURE, 00027 HIGH
SUCTION PRESSURE, or 00028 CHECK
REFRIGERATION SYSTEM occur 3 times within 2
hours.
NO = Normal shutdown rules for above alarms.
ALTERNATOR (Battery
Charger) CHECK SHUTDOWN:
YES / NO YES = When alarm 00051 ALTERNATOR
(BATTERY CHARGER) NOT CHARGING is
activated the alarm light will illuminate and unit will
shut down.
NO = When alarm 00051 ALTERNATOR
(BATTERY CHARGER) NOT CHARGING is
activated the alarm light will illuminate and the unit
will continue to run.
CONFIGURE HOUR METERS
VIEWABLE STANDARD METERS
DISPLAY TOTAL SWITCH ON
HR
YES / NO YES = This hour meter will be displayed during the
startup messaging sequence and will be in hour
meter menu.
NO = This hour meter will not be displayed during
the startup messaging sequence. It will be
displayed with the “other meters and counters”.
DISPLAY STANDBY RUN HR YES / NO YES = This hour meter will be displayed during the
startup messaging sequence and will be in hour
meter menu.
NO = This hour meter will not be displayed during
the startup messaging sequence. It will be
displayed with the “other meters and counters”.
SET PM CONFIGURATIONS
STANDBY RESET VALUE OFF
50 TO 30,000 hours in 50
hour increments
When the standby maintenance hour meter is
reset, the value selected here will be added to the
to the present meter reading to indicate to the
microprocessor when the next service interval
alarm will be activated. If the value entered is “0” the
alarm feature is turned off.
Table 5–1 Configuration Settings
(Refer to Section 5.2.3 for instructions on entering Configuration settings)
Configuration Selections Description