Code number
AHF005 IP00/
IP20
Code
number
AHF010
IP00/IP20
Filter
current
rating
VLT model and current ratings Losses
Acoustic
noise
Frame size
50 Hz
Typical
motor
size
500–550 V
Typical
motor
size
551–690 V AHF005 AHF010
[A] hp [kW]
hp
[kW]
[A] hp [kW]
hp
[kW]
[A] [W] [W] [dBa] AHF005 AHF010
130B5066
+130B5076
130B5331
+130B5332
536
550
[400]
P600
[P450]
504
750
[560]
P650
[P500]
482 3362 2463
130B5198
+130B5199
130B5292
+130B5294
2 x130B5076 2x130B5332
592
600
[450]
P650
[P500]
574
850
[630]
P750
[P560]
549 3704 2576
2 x130B5199 2x130B5294
130B5076
+2x130B5042
130B5332
+130B5333
662
650
[500]
P750
[P560]
642
950
[710]
P850
[P630]
613 4664 2830
130B5199
+2x130B5197
130B5294
+130B5295
4x130B5042 2x130B5333
732
750
[560]
P850
[P630]
743
1075
[800]
P950
[P710]
711 5624 3084
4x130B5197 2x130B5295
3x130B5076 3x130B5332
888
950
[670]
P950
[P710]
866
1200
[900]
P1075
[P800]
828 5556 3864
3x130B5199 3x130B5294
2x130B5076
+2x130B5042
2x130B5332
+130B5333
958
1050
[750]
P1075
[P800]
962
1350
[1000]
P1200
[P900]
920 6516 4118
2x130B5199
+2x130B5197
2x130B5294
+130B5295
6x130B5042 3x130B5333
1098
1150
[850]
P1M0 1079 P1M0 1032 8436 4626
6x130B5197 3x130B5295
Table 5.20 Advanced Harmonic Filters, 500–690 V, 50 Hz