EasyManua.ls Logo

Danfoss VLT AutomationDrive FC 300 - Process PID Control Programming Order

Danfoss VLT AutomationDrive FC 300
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.4.9 Process PID Control Programming Order
Function Par. no. Setting
Initialize the adjustable frequency drive. 14-22 [2] Initialization - make a power cycling - press
[Reset]
1) Set motor parameters:
Set the motor parameters according to the nameplate data. 1-2* As stated on motor nameplate
Perform a full Automation Motor Adaptation.
1-29 [1] Enable complete AMA
2) Check that motor is running in the right direction.
When the motor is connected to adjustable frequency drive with straight forward phase order as U - U; V- V; W - W, the motor shaft
usually turns clockwise as viewed from the shaft end.
Press the [Hand On] LCP key. Check the shaft direction by applying a manual reference.
If the motor turns opposite of the required direction:
1.
Change motor direction in 4-10 Motor Speed Direction
2. Turn off line power - wait for DC link to discharge - switch two
of the motor phases
4-10 Select correct motor shaft direction.
Set configuration mode. 1-00 [3] Process
Set Local Mode Configuration. 1-05 [0] Speed Open-loop
3) Set reference configuration, i.e., the range for reference handling. Set scaling of analog input in parameter 6-**
Set reference/feedback units:
Set min. reference (50 °F [10 °C]):
Set max. reference (176 °F [80 °C]):
If set value is determined from a preset value (array parameter), set
other reference sources to No Function.
3-01
3-02
3-03
3-10
[60] °C] Unit shown on display
23 °F [-5 °C]
95 °F [35 °C]
[0] 35%
Ref
=
Par
. 3 10
0
100
×
Par
. 3 03
par
. 3 02 = 24,
C
3-14 Preset Relative Reference to 3-18 Relative
Scaling Reference Resource [0]=No Function
4) Adjust limits for the adjustable frequency drive:
Set ramp times to an appropriate value as 20 s. 3-41
3-42
20 s
20 s
Set min. speed limits:
Set motor speed max. limit:
Set max. output frequency:
4-11
4-13
4-19
300 RPM
1500 RPM
60 Hz
Set S201 or S202 to desired analog input function (Voltage (V) or milliamps (I)):
WARNING
Switches are sensitive - Make a power cycling keeping default setting of V.
5) Scale analog inputs used for reference and feedback
Set terminal 53 low voltage:
Set terminal 53 high voltage:
Set terminal 54 low feedback value:
Set terminal 54 high feedback value:
Set feedback source:
6-10
6-11
6-24
6-25
7-20
0 V
10 V
23 °F [-5 °C]
95 °F [35 °C]
[2] analog input 54
6) Basic PID settings.
Process PID normal/inverse. 7-30 [0] Normal
Process PID anti wind-up. 7-31 [1] On
Process PID start speed. 7-32 300 rpm
Save parameters to LCP. 0-50 [1] All to LCP
Table 3.11 Example of Process PID Control Set-up
Product Introduction
Design Guide
44 Danfoss A/S © Rev. 2014-02-10 All rights reserved. MG34S222
33

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300

Related product manuals