Electrical Data
Relays
Numbers 4 SPDT
Load at 250 V AC/30 V DC 8A
Load at 250 V AC/30 V DC with cosφ =0.4 3.5 A
Overvoltage category (contact - ground) III
Overvoltage category (contact - contact) II
Combination of 250 V and 24 V signals Possible with one unused relay in between
Maximum thru-put delay 10 ms
Isolated from ground/chassis for use on IT line power systems
Digital Inputs
Numbers 7
Range 0/24 V
Mode PNP/NPN
Input impedance 4 kW
Low trigger level 6.4 V
High trigger level 17 V
Maximum through-put delay 10 ms
Analog Outputs
Numbers 2
Range 0/4–20 mA
Resolution 11 bit
Linearity <0.2%
Analog Outputs
Numbers 2
Range 0/4–20 mA
Resolution 11 bit
Linearity <0.2%
EMC
EMC IEC 61000-6-2 and IEC 61800-3 regarding Immunity of BURST, ESD, SURGE and Conducted Immunity