EasyManua.ls Logo

Dell PowerEdge R660 - Environmental specifications

Dell PowerEdge R660
269 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 25. Supported video resolution options (continued)
Resolution Refresh rate (Hz) Color depth (bits)
1400 x 1050 60 8, 16, 32
1440 x 900 60 8, 16, 32
1600 x 1200 60 8, 16, 32
1680 x 1050 60 8, 16, 32
1920 x 1080 60 8, 16, 32
1920 x 1200 60 8, 16, 32
Environmental specifications
NOTE: For additional information about environmental certifications, refer to the Product Environmental Datasheet located
with the Documentation on www.dell.com/support/home.
Table 26. Continuous Operation Specifications for ASHRAE A2
Temperature Specifications
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
1035°C (5095°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/300 m (1.8°F/984 Ft) above 900
m (2953 Ft)
Table 27. Continuous Operation Specifications for ASHRAE A3
Temperature Specifications
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
540°C (41104°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 85% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/175 m (1.8°F/574 Ft) above 900
m (2953 Ft)
Table 28. Continuous Operation Specifications for ASHRAE A4
Temperature Specifications
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
545°C (41113°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/125 m (1.8°F/410 Ft) above 900
m (2953 Ft)
36 Technical specifications

Table of Contents

Related product manuals