M4000 Insulation Analyzer User Guide
72A-1230 Rev. F 2-19
July 22, 2005
Settling Time Delay- The time, at maximum test voltage, during which the
M4000 samples the data. If it appears that excessive electrostatic interference
is affecting test results, the settling time may be increased in order to sample
the data over a longer period of time. To change the value in this field, click
the mouse in this field and enter in a new value.
Safety Settings - These may be set as desired, provided the option “Restrict
the Safety Configuration settings” was not set during software installation.
If it was, and you want to change these settings, you will have to re-install the
software and de-select that option. It is recommended that unless they are not
functioning, the user should leave the beeper and strobe light operational. The
settings are:
• Beeper - If the beeper is enabled, four beeps will sound when voltage
is applied to a specimen. If the beeper is disabled, there will be no
audible warning of applied voltage.
• Both Low Voltage Leads must be inserted to run test - it is
recommended this box be left unchecked, since most tests require only
one lead.
• Safety Strobe required to run test- If “required to run a test” is
selected, the strobe must be plugged in or a test cannot run. If the
strobe is not available, select “not required”.
• Safety switch must be released between tests - Prevents users from
defeating the purpose of the safety switch by artificially holding it
shut. The switches should be pressed when the message onscreen tells
you to.
Click on the OK button to accept your selection.
Advanced Configuration
When the Advanced tab is selected, the following is displayed: