EasyManua.ls Logo

Eaton easy800

Eaton easy800
394 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Function blocks
5.6 C, counter relay
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 165
Legend for Figure 112:
1: Counter coil C..C_
2: Upper setpoint value >SH
3: Start value >SV.
4: Lower setpoint value >SL.
5: Counting direction, coil C..D_
6: Transfer start value, coil C..SE.
7: Reset coil C..RE
8: Contact (N/O) C..OF: Upper limit setpoint reached, exceeded
9: Contact (N/O) C..FB lower limit setpoint reached, undershot
10: Actual value equal to zero.
11: Out of value range
Range A:
The counter range has the value zero.
The contacts C..ZE (actual value equal to zero) and C..FB (lower setpoint value undershot) are active.
The counter receives pulses and increases the actual value.
C..ZE drops out as well as C..FB after the lower setpoint value is reached.
Range B:
The counter relay counts upwards and reaches the upper setpoint value.
The “upper setpoint value reached” contact C..OF becomes active.
Range C:
The coil C..SE is briefly actuated and the actual value is set to the start value.
The contacts go to the respective position.
Range D:
The counting direction coil C..D_ is actuated.
If counting pulses are present, downward counting is initiated.
If the lower setpoint value is undershot, the contact C..FB becomes active.
Range E:
The reset coil C..RE is activated. The actual value is set to zero.
The contact C..ZE is active.
Range F:
The actual value goes outside the value range of the counter relay.
The contacts OF, FB, ZE become active according to the direction of the values (positive or negative).
Memory
52 + per 4 Byte/Constant at function block input
Cycle time [μs]
easy800 standard easy800-SWD
46 12

Table of Contents

Related product manuals