12 Appendix
12.3 Technical data
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 349
12.3.5 Inputs
12.3.5.1 Digital inputs 115/230 V AC
EASY819-AC-RC.
Digital inputs 115/230 V AC
Number
12
Status indicator
LCD display (if provided)
Potential isolation
from power supply no
between digital inputs
no
from the outputs
yes
to PC interface (COM), memory card, network NET,
easyLink
yes
Rated operating voltage L (sinusoidal)
at signal ”0” V AC 0 – 40
at signal ”1” V AC
79 – 264
Rated frequency Hz
50 – 60
Input current at signal "1"
I1 to I6, I9 to I12 m A 10 x 0.25 (at 115 V AC, 60 Hz)
10 x 0.5 (at 230 V AC, 50 Hz)
I7, I8 m A
2 x 4 (at 115 V AC, 60 Hz)
2 x 6 (at 230 V AC, 50 Hz)
Delay time
Delay time (0 – 1/1 – 0) I1 - I6, I9 - I12
Debounce ON, 50/60 Hz ms 80 66
Debounce OFF, 50/60 Hz ms
20 16
Delay time I7, I8 (1 – 0)
Debounce ON, 50/60 Hz ms 120 100
Debounce OFF, 50/60 Hz ms
4033
Delay time I7, I8 (0 –> 1)
Debounce ON, 50/60 Hz ms 8066
Debounce OFF, 50/60 Hz ms
2016
Max. admissible cable length (per input)
I1 to I6, I9 to I12
Debounce ON m Normally 100
Debounce OFF m
Normally 60
I7, I8 m
Normally 100

Table of Contents