2 Installation
2.8 Connecting the serial interface
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 61
The following chapters show the permissible cables for connecting your
easy800 device via the serial interface.
2.8.1 Connection to a PC
Connect one of the following programming cables to the COM or USB
interface of your PC and to the serial interface of the easy800 device.
Table 3: Programming cable for the connection to a PC
Device Programming cable Baud Rate
easy800 standard EASY800-PC-CAB 19.2 kBaud
easy800 standard
EASY800-USB-CAB 57.6 kBaud
easy800 standard
EASY800-MO-CAB 57.6 KBaud, universal high-speed cable
easy800-SWD
EU4A-RJ45-USB-CAB1 57.6 kBaud
Figure 59:Fitting the programming cable to
an easy800 standard
Figure 60:Fitting the programming cable to an
easy800-SWD device
CAUTION
When connecting the programming cable, the easySoft-Pro
programming software must be offline. On no account should
the programming cable be moved from one easy800 device to
another when the connection is online.