EasyManua.ls Logo

Eaton easy800

Eaton easy800
394 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Installation
2.6 Connecting outputs
50 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Connecting transistor outputs of the expansion unit
Figure 51:Digital transistor outputs EASY6..-DC-TE and EASY4...-DC-TE
a EASY4... -DC-TE
b EASY6... -DC-TE
2.6.3 Connect analog output
All easy800 standard devices with a 24 V DC supply voltage have an analog
output QA 01. QA 01 can be used to output a DC voltage from 0 - 10 V, with
a 10-bit resolution, value range 0 - 1023.
On the easy800 standard from device version 02, it is also possible to
connect the EASY406-DC-ME and EASY411-DC-ME DC expansion units with
an analog output ( Section “Connecting DC inputs of the EASY4..-DC-ME
expansion units“, Page 39).
The analog output can be used, for example, for controlling solenoid valves
and other actuators.
Observe the hazard warnings concerning the processing of analog signals
( section 2.5.2, “Connecting analog inputs”, page 40) and the note
concerning the same reference potential (chassis ground).
F 10 A
f 2.5 A
0 V H
0 V
Q
24 V
Q
aa
b
(20.4 – 28.8 V H)
+ 24 V H
RL
5 W/24 V
0.5 A
24 V H
0.5 A

Table of Contents

Related product manuals