11 What Happens If …?
11.5 Functionality of the NET faulty
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 337
800-SWD after pressing the configuration button
In this case, the actual configuration matches the target configuration.
11.5 Functionality of the NET faulty
Table 24: Checking the functionality of the NET using the NET LED
Config-LED
Meaning
Green flashing A station of the project configuration was replaced by a compatible station in the target
configuration. The replacement is permitted by the “Compatible devices permissible”
device parameter being clicked.
red continuous light
Configuration error: the target configuration does not match the project configuration.
Possible causes:
The SWD station of the project configuration was replaced by a incompatible station.
SWD station was replaced by a compatible station, but the “Compatible devices
permissible” device parameter has not been clicked.
The station was replaced by an universal module, but the “Replaceable with
universal module” device parameter has not been clicked
CAUTION
You can make a visual check the functionality of the NET by
means of the NET LED and in the circuit diagram via diagnostics
bit ID01-ID08.
Status of the NET
LED
Meaning
Off NET not operational, fault in configuration
Continuous light
NET station fault, possible causes:
Net is initialized and at least one station has not been detected. Check the plug-in
connections.
You have modified the NET ID or baud rate for at least one station after the
configuration has been completed. Change the configuration.
You have deleted
the program on a NET station and thus also its NET configuration,
Page 94. Recongure the NET via station 1.
You have expanded an existing NET station and replaced it with a new device which
cannot be assigned parameters.
Flashing
NET operating fault-free
Event
Explanation Remedy
easy800 standard cannot
configure EC4P easyControl
devices reliably (NET
parameters).
Synchronization between the devices Set the NET parameters directly
on the EC4P.