12 Appendix
12.3 Technical data
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 353
12.3.6 Outputs
12.3.6.1 Relay outputs
EASY8..-R...
Number 6
Outputs in groups of
1
Parallel switching of outputs to increase
performance
Not permissible
Protection of an output relay
Miniature circuit-breaker B16 or
fuse 8 A (slow).
Potential isolation
from power supply yes
from the inputs
yes
to PC interface, memory card, network NET,
easyLink
yes
Safe isolation V AC 300
Basic isolation V AC
600
Lifespan, mechanical Opera-
tions
10 x 10
6
Contacts
conventional thermal current (UL/CSA) A 8 (10)
Recommended for load: 12 V AC/DC m A
> 500
Short-circuit proof p.f. = 1,
characteristic B16 at 600 A
A
16
Short-circuit proof cos ϕ = 0.5 - 0.7;
characteristic B16 at 900 A
A
16
Rated impulse withstand voltage U
imp
contact to coil
kV
6
Rated operational voltage U
e
V AC
250
Rated insulation voltage U
i
V AC
250
Safe isolation to EN 50178 between coil and
contact
V AC
300
Safe isolation to EN 50178 between two
contacts
V AC
300
Making capacity, IEC 60947
AC–-15, 250 V AC, 3 A (600 ops./h) Operations 300000
DC-13, L/R 150 ms, 24 V DC, 1 A (500 S/h) Operations
200000
Breaking capacity, IEC 60947
AC-15, 250 V AC, 3 A (600 ops./h) Switch
operations
300000
DC-13, L/R 150 ms, 24 V DC, 1 A (500 S/h) Switch
operations
200000

Table of Contents