12.3 Technical data
354 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Filament bulb load
1000 W at 230/240 V AC Switch
operations
25000
500 W at 115/120 V AC Switch
operations
25000
Fluorescent lamp load
Fluorescent lamp load 10 x 58 W at
230/240 V AC
With upstream electrical device Switch
operations
25000
Uncompensated Switch
operations
25000
Fluorescent lamp load 1 x 58 W at
230/240 V AC, conventionally compensated
Switch
operations
25000
Switching Frequency
Mechanical operations Switch
operations
10x 10
6
Switching Frequency Hz
10
Resistive load/lamp load Hz
2
Inductive load Hz
0.5
UL/CSA
Continuous current at 240 V AC A 10
AC
Control circuit rating codes (utilization
category)
B 300 Light Pilot Duty
Max. rated operational voltage V AC
300
max. thermal continuous current cos ϕ = 1
at B 300
A
5
max. make/break cos ϕ capacity 1 at
B300
VA
3600/360
DC
Control circuit rating codes (utilization
category)
R 300 Light Pilot Duty
Max. rated operational voltage V DC
300
Max. thermal continuous current at R 300 A
1
Max. make/break capacity at R 300 VA
28/28