12 Appendix
12.3 Technical data
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 355
12.3.6.2 Transistor outputs
The transistor outputs on easy800-SWD can alternatively also be configured
as inputs.
EASY8..-DC-T..., easy800-SWD
Number of device outputs easy800 standard: 8 (Q1-Q8)
easy800-SWD: 2 (Q1/Q2)
Outputs of SWD stations
easy800 standard: none
easy800-SWD: 83 (Q17-Q99)
Power supply of the transistor outputs on
easy800 standard:
Rated operational voltage Ue V DC 24
permissible range Ue V DC
20.4 – 28.8
Residual ripple %
5
Supply current
at signal ”0” typ.⁄max. m A 18/32
at signal ”1” typ.⁄max. m A
24/44
Protection against polarity reversal
yes
Caution!
If voltage is applied to the outputs of easy800 standard when the
polarity of the supply voltage is reversed, this will result in a short-
circuit.
Power supply of the transistor outputs on easy800-SWD: Corresponds to the DC power supply of
the device (→ section “12.3.3.2
Voltage supply: DC”, page 346)
Potential isolation
from power supply EASY8...-DC-T...: yes
easy800-SWD: no
from the inputs
EASY8..-DC-T...: yes
easy800-SWD: no
to the PC interface (COM), memory card,
easyNet, easyLink, AUX
yes
to SWD
easy800-SWD: no
Rated operational current at signal “1”,
maximum
Ie
A
easy800 standard: 0.5
easy800-SWD: 0.1
Lamp load without R
v
W
easy800 standard: 3 (Q1 – Q4),
5 (Q5 – Q8)
easy800-SWD: 1.2
Residual current at signal “0” per channel m A
< 0.1
Max. output voltage
With condition “0” at external load
<10MΩ
V 2.5
on 1 signal at
easy800 standard: I
e
= 0.5 A
easy800-SWD: I
e
= 0.1 A
V
easy800 standard: U = U
e
-1 V
easy800-SWD: U = U
e
-2 V