12 Appendix
12.3 Technical data
346 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
12.3.3 Power supply
12.3.3.1 AC Power supply
12.3.3.2 Voltage supply: DC
EASY8..-AC-..
Rated operational voltage
Rated value (sinusoidal)
Ue
V AC,
(%)
100/110/115/120/230/240 AC (+10/-15)
permissible range V AC
85 - 264
Frequency, tolerance Hz (%)
50/60 (± 5)
Input current consumption
At 115/120 V AC 60 Hz m A
Normally 70
at 230/240 V AC 50 Hz m A
Normally 35
Voltage dips, IEC/EN 61131-2 ms
20
Heat dissipation
At 115/120 V AC VA Normally 10
at 230/240 V AC VA
Normally 10
EASY8..-DC-.., easy800-SWD
Rated operational voltage
Rated value U
e
V DC,
(%)
24 DC (-15/+20)
permissible range
1)
V DC
20.4 - 28.8
Residual ripple %
5
Protection against polarity
reversal
yes
Input current
At rated operating voltage m A easy800 standard: 140
EASY802-DC-SWD: 500
EASY806-DC-SWD: 900
Inrush current and duty factor
easy800-SWD: 12.5 A for 6 ms
Voltage dips (IEC/EN 61131-2) ms
10
Heat dissipation
At 24 V DC W easy800 standard: normally 3.4
EASY802-DC-SWD: max 5
EASY806-DC-SWD: max. 6
Fuse A
1 to 4
easy800-SWD: 3
1) Use power feed modules if the cable length of the SWD line causes excessive voltage drop.