12 Appendix
12.3 Technical data
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 345
Air discharge kV
8
Contact discharge kV
6
Electromagnetic fields (RFI), to
IEC EN 61000-4-3
0.8 - 1.0 GHz V/m 10
1.4 - 2 GHz V/m
3
2.0 - 2.7 GHz V/m
1
Radio interference suppression
EN 55011 Class B
Burst,
to IEC EN 61000-4-4
Supply cables kV 2
Signal cables kV
2
easyNet kV
2
SWD-line kV
2
Power pulses (surge),
to IEC EN 61000-4-5
(supply cables, symmetrical)
kV
easy8..-AC: 2
easy8..-DC: 1
easySWD: 1
radiated RFI,
to IEC EN 61000-4-6
V 10
Insulation resistance
Overvoltage category
III
Pollution degree
2
Clearance in air and creepage
distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Tools and terminal capacity
Solid, minimum to maximum mm
2
easy800 standard: 0.2 – 4 (AWG 22 – 12)
easy800-SWD: 0.2 to 1.5
(AWG 24 -16)
Flexible with ferrule, minimum to
maximum
mm
2
easy800 standard: 0.2 – 2.5 (AWG 22 – 12)
easy800-SWD: 0.2 to 1.5
(AWG 24 -16)
Tools
easy800 standard
standard screwdriver mm 3.5 x 0.8
standard screwdriver inch
0.14 x 0.03
max. tightening torque Nm
0.6
easy800-SWD
No tool required, due to push-in terminals