EasyManua.ls Logo

Eaton easy800

Eaton easy800
394 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Installation
2.5 Connecting the inputs
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 31
2.5.1 Connecting the digital inputs
Connecting the AC inputs of the 800 standard
Figure 21:Connecting easy800 standard
Input signal voltage range
Off signal: 0 to 40 V.
On signal: 79 to 264 V
Input current
I1 to I6, I9 to I12: 0.5 mA/0.25 mA at 230 V/115 V.
I7, I8: 6 mA/4 mA at 230 V/115 V.
Connecting AC inputs of the expansion unit EASY618-AC-RE
Figure 22:Connecting inputs on the easy618-AC-RE AC expansion unit
Connect the inputs, for example, to pushbutton actuators, switches or
relay/contactor contacts.
DANGER
Connect the inputs for AC basic and expansion units in
accordance with the safety regulations of VDE, IEC, UL and CSA
with the same phase conductor that provides the power supply
voltage. The device will otherwise not detect the switching level
or may be destroyed by overvoltage.
...
l1 I2 I7
L
N
LNN
115/230 V h
F1
l3 I4 l5 I6
L
N
R10R9R8R7R6R5R4R3R2R1E+ E–
R11
R12 NNL
115/230 V h
F1

Table of Contents