11 What Happens If …?
11.3 Event
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 335
11.3 Event
Event
Explanation Remedy
The actual values are not
being stored retentively.
Retention has not been switched on. Switch on retention in the
SYSTEM menu.
The RETENTION… menu is
not displayed in the SYSTEM
menu.
easy800 is in RUN mode Select STOP mode
The retentive data is cleared
when there is a mode change
from RUN to STOP.
This behavior only occurs when using the
PW02 (pulse width modulation) function
block in easy800 standard.
Avoid using the PW02 function
block.
The SYSTEM menu is not
displayed.
This easy800 Type model does not have this
menu.
easy800 exchange if you need
retention
When the device is switched
on, the easy800 switches to
STOP mode
No circuit diagram in the easy800 Load, input circuit diagram
RUN START is deactivated at easy800
standard.
Activating RUN mode in Menu
SYSTEM.
The contacts of the BC (data
block comparison) and block
transfer (BT) function blocks
flash in the power flow
display
The display of the easy800 standard is being
updated to intermediate states too
frequently although the contacts are
operating properly
Ignore this section of the power
flow display.
LCD display showing nothing.
No supply voltage Switch on the power supply
easy800 defect Press the OK button. If no menu
appears, replace the easy800
device.
Text displayed with too many spaces Enter text or do not activate text
output
GW flashes on the Status
display
EASY200-EASY bus coupler detected
without I/O expansion
Connect I/O expansion to
external easyLink
The switching devices are
not working
No supply voltage at AUX Switch on the supply voltage at
AUX