12 Appendix
12.3 Technical data
352 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
12.3.5.3 Analog inputs
easy800 standard
DC version
Number 4 (I7, I8, I11, I12)
Potential isolation
from power supply no
to the digital inputs
no
from the outputs
yes
to PC interface, memory card,
network NET, easyLink
yes
Input type
DC voltage
Signal range V DC
0 – 10
Resolution, analog V
0.01
Resolution, digital V
0.01
Resolution, digital Bit
10 (value 0 – 1023)
Input impedance kΩ
11.2
Accuracy of actual value
two easy800 standard devices ± 3% ± 0.12 V
Within a single device
± 2% ± 0.12 V
Conversion time, analog/digital
Debounce ON: ms 20
Debounce OFF ms
each CPU cycle
Input current m A
< 1
Cable length screened m
< 30