12 Appendix
12.3 Technical data
350 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
12.3.5.2 Digital inputs 24 V DC
The transistor inputs I3 and I4 on EASY806-DC-SWD can alternatively also be
configured as outputs Q1 and Q2.
easy800 standard
DC version
EASY806-DC-SWD
Number of device inputs 12 (I1 - I12) 4 (I1 - I4)
Inputs of the SWD stations
None 83 (I17-I99)
Inputs can be used as
analog inputs
4 (I7, I8, I11, I12) None
Status indicator
LCD display (if provided) LED
Potential isolation
from power supply no no
between digital inputs
no no
from the outputs
yes no
to PC interface (COM), memory card, easyLink
no yes (if provided)
to easyNet
yes yes
to AUX
not available
yes
to SWD
not available no
Rated operational voltage U
e
V DC
24 24
at signal ”0” U
e
V DC
< 5 (I1 – I6, I9, I10)
< 8 (I7, I8, I11, I12)
< 5 (I1 – I4)
at signal ”1” U
e
V DC
> 15.0 (I1 – I6, I9, I10),
> 8.0 (I7, I8, I11, I12)
> 15.0 (I1 – I4)
Input current at signal ”1”
m A 3.3 (at 24 V DC)
(I1 to I6, I9, I10)
3.9 (to 24 V DC)
(I1-I4)
m A
2.2 (at 24 V DC)
(I7, I8, I11, I12)
Hardware delay time ”0“ -> „1“
Debounce ON ms 20 20
Debounce OFF ms
Normally 0.025 (I1 – I4)
normally 0.25 (I5, I6, I9, I10)
normally 0.15 (I7, I8, I11, I12)
max. 0.02
Hardware delay time ”1“ -> ”0“
Debounce ON ms 20 20
Debounce OFF ms
Normally 0.025 (I1 - I4)
normally 0.25 (I5, I6, I9, I10),
normally 0.15 (I7, I8, I11, I12)
max. 0.02 (I1-I4)
Cable length (unscreened) m
100 100