5 Function blocks
5.32 T, timing relay
256 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Operating mode
This parameter defines the switch function of the timing relay:
1) Only when using an easy800 standard control relay from device version 04 or easy800-SWD from device
version 01.
Time Range
The function block parameter determines in which time range and at which
resolution the relay operates.
T 02
Function block: Timing relay, number 02
X
Operating mode: On-delayed
m:s
Time range: Minute: Seconds
+
Parameter set can be called via the PARAMETERS menu
>I1
Setpoint 1
>I2
Setpoint 2 (for relay functions with 2 times)
QV>
Display: Elapsed time
Parameters
Switch function
X On-delayed switching
?X
On-delayed switching with random time range
â
Off-delayed switching
?â
Off-delayed switching with random time range
Xâ
On- and off-delayed
#
Off-delayed with random time range, setpoint retriggerable 1)
?#
Off-delayed with random time range, retriggerable 1)
?Xâ
On- and off-delayed switching with random time, 2 time setpoints
ü
Pulse shaping switching
Ü
Flashing, synchronous, 2 setpoints
Ü
Flashing, asynchronous, 2 setpoints
Parameters Time range and setpoint Resolution
S 000.00 Seconds; 0.05 to 999.995 s for constants and variable values 5ms
M:S 00:00
Minutes:Seconds; 00:00 to 99:59 only for constants and variable values 1s
H:M 00:00
Hours:Minutes; 00:00 to 99:59 only for constants and variable values 1min
Minimum time setting: 0.005 s (5 ms)
If a setpoint value is less than the easy800 cycle time, the
elapsed time will only be recognized in the next cycle.