5 Function blocks
5.32 T, timing relay
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 259
Timing relay, on-delayed with and without random switching
Random switching:
The contact of the timing relay switches randomly within the setpoint value
range.
Figure 188:Signal diagram of timing relay, on-delayed (with and without random switching)
1: Trigger coil T…EN
2: Stop coil T…ST
3: Reset coil T…RE
4: Switching contact (N/O contact) T…Q1
t
s
: setpoint time
Range A: The time runs down from the set time value.
Range B: The time does not elapse because the trigger coil drops out prematurely.
Range C: The Stop coil stops the time from elapsing.
Figure 189:Signal diagram of timing relay, on-delayed (with and without random switching)
Range D: The stop coil is inoperative after the time has elapsed.
Range E: The reset coil resets the relay and the contact.
Range F: After the reset coil is activated, the switching contact is switched off and the internal time
counter is reset. The function relay waits for a new trigger pulse.
t
1
+ t
2
= t
s
t
A
B
t
s
1
2
4
3
C
t
F
D
E
t
s
1
2
4
3
t
s
F

Table of Contents