5 Function blocks
5.32 T, timing relay
262 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Figure 194:Operational diagrams timing relay, on and off delayed 3
Range H: The Reset signal interrupts the timing out of the set time.
Timing relay, single pulse
Figure 195:Signal diagram timing relay, single pulse 1
1: Trigger coil T…EN
2: Stop coil T…ST
3: Reset coil T…RE
4: Switching contact (N/O contact) T…Q1
Range A: The trigger signal is short and is lengthened.
Range B: The trigger signal is longer than the set time.
Range C: The stop coil interrupts the timing out of the set time.
Figure 196:Operational diagram timing relay, pulse shaping 2
Range D: The reset coil resets the timing relay.
Range E: The reset coil resets the timing relay.
The trigger coil is still energized after the reset coil is disconnected, whilst the delay time runs down.
H
t
1
2
4
3
t
s1
A B
t
1
+ t
2
= t
s
t
s
t
s
C
1
2
4
3
t
D
E
t t
s
1
2
4
3