7 SmartWire-DT
7.3 SWD device parameters
290 Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Table 19: Summary of SWD device parameters
Device parameter
definable on
SmartWire-DT reaction
with option activated
easy800-SWD
Stop on SWD error easy800-SWD behaves as follows in the event of SWD error and
with option activated: easy800-SWD switches to STOP mode.
with option deactivated: easy800-SWD stays in RUN mode, the circuit diagram
continues running.
All devices are
optional
The activated option causes the “Mandatory station” option adjustable on the station
to be no longer taken into account. The SWD line can be run with any number of failed
SWD stations.
A missing SWD station causes
the PRSNT diagnostic bit to be set to 0
the DIAG diagnostic bit to be set to 1
with the option activated, that no SWD error is reported,
with the option deactivated, that easy800-SWD checks the set “Mandatory station”
device parameter.
SWD station
Compatible devices
permissible
If easy800-SWD checks this option, it has already determined that an “incorrect”
SWD station is present and that the station is not a universal module.
easy800-SWD checks the option whether compatible devices are permissible.
With the activated option, easy800-SWD checks whether the station found is
compatible with the station expected by the target configuration.
If this is the case, no SWD error is reported.
If the station found is not compatible, an SWD error is reported.
with the option deactivated, the SWD error is reported
Compatible stations are shown in Table 12.6Page 363.
Required station
This device parameter is only evaluated if the “All devices are optional” parameter is
not clicked on easy800-SWD.
A missing SWD station causes
with the option activated, an SWD error to be reported.
with the option deactivated, no SWD error to be reported
Replaceable with
universalmodule
An “incorrect” SWD station causes easy800-SWD to check whether the SWD station
present is a universal module. If this is the case, the SUBST diagnostic bit is set to 1.
Furthermore
with the option activated, no SWD error is reported.
with the option deactivated, an SWD error is reported, easy800-SWD switches to
STOP mode and the data exchange is interrupted.
If the SWD station present is not a universal module, easy800-SWD checks whether the
“Compatible devices permissible” option is activated.