12 Appendix
12.3 Technical data
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 357
Other inductive loads:
easy800-SWD:
DC13
T
0.95
= 72 ms
R = 48
L = 1.15 H
Utilization factor g =
0.25
Relative duty factor %
100
Max. switching frequency
f = 0.5 Hz
Max. duty factor
DF = 50 %
Switching
operations/h
1500
T
0.95
= 15 ms
R = 48
L = 0.24 H
Utilization factor g =
0.25
Relative duty factor %
100
Max. switching frequency
f = 0.5 Hz
Max. duty factor
DF = 50 %
Switch
operations/h
1500
Inductive loading with external suppressor circuit for each load
( section “2.6.2 Connecting transistor outputs”, page 48)
Utilization factor g = 1
Relative duty factor %
100
Max. switching frequency
Max. duty factor
Switch
operations/h
Depending on the
suppressor circuit
(according to
EN 60947-5-1)
DC13, DC14
T
0.95
= 15 ms
R = 240
L = 1.15 H
Simultaneity factor g
1
Relative duty factor %
100
Max. switching frequency
at maximum duty factor DF = 50 %
Hz
10