2 Installation
2.5 Connecting the inputs
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 33
Two-wire proximity switches have a residual current in the 0 state. If this
residual current is too high, the device only detects the 1 state at the input.
With two-wire proximity switches or sensors with similar residual current
consumption use therefore the inputs I7 and I8.
Use an additional input circuit if several inputs are required with a higher
input current.
Increased input current
The following input circuit can be used in order to prevent interference and
also when using two-wire proximity switches:
Figure 24:Increasing the input current on the easy800 standard AC version
Figure 25:Increasing the input current at the AC expansion unit EASY618-AC-RE
A resistor can be connected in series with the circuit shown in order to
restrict the inrush current.
When using a 100 nF capacitor, the drop out delay of the input
increases by 80 (66.6) ms at 50 (60) Hz.
115/230 V h
L
F1
N
LN
I1
100 nF/275 V h
L
N
R10R9R8R7R6R5R4R3R2R1E+ E– R11 R12 NNL
115/230 V h
F1
100 nF/275 V h