3 Commissioning
3.9 Configuring the analog expansion unit
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 85
EASY406-DC-ME
Figure 77:Configuration code EASY406-DC-ME (three-digit)
Factory setting = 111
(analog input 1 and 2 are activated, both for 0 - 10 V as well as the analog
output). Marker words MW93 - MW95 are therefore assigned ( Table 9,
Page 87).
With EASY406-DC-ME you can activate and commission a voltage, current or
temperature input for analog value 1 and 2.
EASY411-DC-ME
Figure 78:Configuration code EASY411-DC-ME (four-digit)
Factory setting = 3333
(analog input 1 to 6 as well as analog output 1 and 2).
Marker words MW89 - MW96 are therefore assigned ( Table 9, Page 87).
With EASY411-DC-ME you can activate and commission all six analog inputs
(voltage, current or temperature) at the same time.
XXX
X: 1. analog input:
0 = off
1 = 0 - 10 V
2 = 0 - 20 mA
3 = PT100 resistance sensor
X: 2. analog input
0 = off
1 = 0 - 10 V
2 = 0 - 20 mA
3 = PT100 resistance sensor
X: analog output:
0 = off
1 = ON
XXXX
X: 0 - 10 V, 1. and 4. analog input:
0 = both off
1 = 1. analog input on
2 = 4. analog input on
3 = 1 + 4. analog input on
X: 0 - 20 mA, 2. and 5. analog input:
0 = both off
1 = 2. analog input on
2 = 5. analog input on
3 = 2. + 5. analog input on
X: PT100 resistance sensor, 3. und 6. input:
0 = both off
1 = 3. analog input on
2 = 6. analog input on
3 = 3. + 6. analog input on
X: 1. and 2. analog output:
0 = both off
1 = 1. analog output on
2 = 2. analog output on
3 = 1. + 2. analog output on