7. System settings
7.5 NET
Bus delay
The bus delay is used to define the time after which a station on the NET will send its
data to other stations.
This bus delay needs to be adjusted as appropriate for the number of stations and the
values being transmitted. Please note than an excessively short bus delay will result
in data collisions.
The permissible value range for the bus delay is 10 ms to 255 ms.
Cyclical data will be sent every 10 ms or when there is a data change, but not before
the bus delay has elapsed. Using the default value of 60 ms will normally be sufficient
to prevent transmission overloads.
Remote RUN
If this field is enabled, the NET stations of a group with NET-IDs 02 through 08 will
take their current RUN or STOP operating mode from the NET station with NET-ID 1.
See also
 → Section "Setting up a NET group", page 706
624