Protection
Contextual help of the web interface – 67
Shutdown on power outage powerOutagePolicy/Settings panicShutdownTrigger
s
onLowStateOfCharge true/false
restart enabled true/false
powerOutagePolicy/
suppliersSettings
id 1: Primary
2: Group 1
3: Group 2
settings localShutdownDuration [time in seconds]
shutdownTriggers/
powerOutage
enabled true/false
capacityLessThan [percentage]
afterBackupTime [time in seconds]
startShutdownBeforeEndOf
Backup
[time in seconds]
endShutdownBeforeEndOfB
ackup
[time in seconds]
3.5.3.3.1 Additional information
3.5.3.4 Troubleshooting
Action not allowed in Control/Schedule/Power outage policy
Symptom
Below message is displayed when you access the Control, Schedule or Power outage policy page.
This action is not allowed by the UPS.
To enable it, please refer to the user manual of the UPS and its instructions on how to configure the UPS settings and allow
remote commands.
Possible Cause
1- Remote commands are not allowed due to the UPS configuration (see the action below)
2- The UPS does not support remote commands.
Action
Refer to the UPS user manual and its instruction on how to configure the UPS settings and allow remote commands.
Example: UPS menu Settings>>>ON/OFF settings>>>Remote command>>>Enable.
For details on Save and Restore, see the Save and Restore section.