Specifications of CI 3000 / SIOX
122
Version 2.09 09. April 2014
1)
Warning - hazardous electrical voltage!
Danger of electric shock! BEFORE and AFTER connection it must checked
that the 230 V AC relay outputs are off load!
Low voltage and safety extra-low voltage must not be applied together at the relay outputs 15/16/18,
25/26/28 and 35/36/38.
2)
See also Section 5.5.2
CI 3000 Store Computer SIOX Extension Module
Front switch 1 x N.O. 230 V AC, with external connec
tion option, floating
Max. 2.4 A for incandescent lamps
Max. 4 A for inductive load
Max. 6 A for ohmic load
-
Fieldbus port CAN bus, floating
Data ports 1 x Data port for SIOX Extension Module Internal port to CI 3000
2 x serial RS232 (SUB-Min-D), floating
- MODEM:
Interface to modem or PC
- COM2:
for the connection of UA 30/Dixell control
lers, AHT cases with external controllers,
M-bus or as an interface for building auto
mation
-
CI 3100 ONLY:
In additional, 1 x serial RS232, floating:
- COM3 - for the connection of
UA 30/Dixell controllers
Archive memory Standard 2 MB, 6 MB or 16 MB
Battery-backed (lithium cell)
-
CI 3100: 6 MB or 16 MB,only
Battery-backed (lithium cell)
Monitoring function Watchdog
Real-time clock Battery-backed (lithium cell)
Accuracy typ. 12 min/yr at 25 °C
With/without manual control switch approx.
800 g
Temperature range Transport: -20 °C ... +80 °C
Operation 0 °C ... +50 °C
The device must be protected from direct sunlight!
Temperature change Transport: max. 20 K/h
Operation max. 10 K/h
Relative humidity
(non-condensing)
Transport: 8 % ... 80 %
Operation 20 % ... 80 %
Shock
to DIN EN 60068-2-27
Transport and operation 30 G
Vibration 10 - 150 Hz
to DIN EN 60068-2-6
Transport and operation 2 G