Operation of CI 3000
69
Version 2.09 09. April 2014
7.2.2 Superuser mode (granting Superuser rights)
Superuser mode is reserved exclusively for use by service personnel!
With activated setpoint interlock (restricted setpoint changes) a password is necessary.
For detailed instructions see menu 9-3.
Before any values can be entered, the entry block must be deactivated as follows:
‐ In the Main Menu choose item 9 Parameter Setting.
‐ In this menu choose item 3 Block.
‐ Enter the current date in reverse order (not shown on display).
‐ Press the ENTER key (↵) to confirm, indicated by ”S” displayed on the screen.
‐ Press the ESC key to exit the screen.
Example:
The current date is April 17, 2035, which in order of day-month-year is 17.04.35. In this instance the entry re
quired to grant Superuser rights is 534071.
7.2.3 Service-Modus
Activating service mode
Service mode is reserved exclusively for use by service personnel!
With activated setpoint interlock (restricted setpoint changes) a password is necessary.
For detailed instructions see menu 9-3.
Service mode enables the service technician to suppress the remote alarm function of the Store Computer for a
limited time while carrying out maintenance of repair work (see Section 3.1.2).
‐ In the Main Menu, choose 9 Parameter Setting.
‐ From this menu item choose 3 Block.
‐ Simultaneously press the MODE + ENTER (↵) keys to open the screen for suppressing remote alarm and
enter the time required for service work (1 to 255 min.).
‐ The service mode only remains active for the duration entered above.
Any alarms (Priority 1 and 2) still active when the set service mode time expires cause the audible
signalling devices and alarm relays to be actuated and are forwarded by automatic fault report trans
mission.
Deactivate service mode
Service mode can be reset/cancelled by entering a time of 0 min.