Alarms and Messages of CI 3000
115
Version 2.09 09. April 2014
10 Alarms and Messages of CI 3000
No. Messages Cause Correction
Hardware faults
0
int. error 01 0000 CPU hardware problem With repeated occurrence replace
the device
int. error 02 0000 CPU or ROM hardware problem With repeated occurrence replace
the device
int. error 04 0000 Problem with the archiving
(invalid information structures in RAM)
Delete the operating archive with
MODE + ESC + 6
if required delete the meter archive
with MODE + ESC + 3
int. error 08 0000 CPU or ROM hardware problem With repeated occurrence replace
the device
int. error 10 0000
int. error 20 0000
Stack error – can only occur in developer ver
sion, otherwise CPU or ROM hardware problem
With repeated occurrence replace
the device
int. error 40 001A Problem with the archiving
(invalid information structures in RAM)
Delete the meter archive with
MODE + ESC + 3
int. error 40 0010
int. error 40 0011
int. error 40 0012
int. error 40 0013
int. error 40 0014
int. error 40 0021
Problem with the archiving
(invalid information structures in RAM)
Delete the operating archive with
MODE + ESC + 6
int. error 80 0000 CPU or ROM hardware problem With repeated occurrence replace
the device
1 ROM Fault
or
Hardware Fault Mxx
A chip for saving the configuration is defect.
The AHT case with Danfoss controller has a
fault
Replace device
Check device Mxx
2 RAM Fault A chip for saving the configuration is defect. Replace device
3 RAM Battery Def. RAM battery failure while controller off. Notify Service Organization
4 EEPROM Fault Configuration saving component defect. Replace device
5 EEPROM Contents Configuration data in EEPROM implausible. Please contact Service Organization
6 FLASH Error Configuration saving component defect. Replace device
7 FLASH I Cont. Fault Configuration data in FLASH memory implausi
ble.
Please contact Service Organization