Function of CI 3000
26
Version 2.09 09. April 2014
4.9 EU archive
The Store Computer automatically archives the current operating data of all LDS components, see also chapter
4.8.
In addition, it is possible to archive the temperatures and states of individual refrigeration points according to the
EU directive. The configuration is carried out under menu 6-1-5. The archived data can be read out via modem
or PC and presented in a chart or a graph using the PC software LDSWin.
Operating data of LDS components is archived in a ring buffer for periods of one week (case/coldroom con
trollers, e.g. UA 300/UA 400) or one day (pack controllers, e.g. VS 3010). Hourly and daily averages are addi
tionally produced for pack controller operating data and are likewise archived in ring buffers for periods of a
week or year. EU archives cover a period of one year.
It is recommended to call up all operating data recorded in the store computer on a cyclical basis
using scripts from within the PC software LDSWin. This has the advantage that all relevant operating
data (e.g. the HACCP demanded by legislation) is backed up on a second system which can be
used to provide a record of the temperatures if required.
4.9.1 Archive memory requirements
Three versions of the CI 3000 Store Computer are available at the present time, differing by size of data mem
ory (2 MB, 6 MB or 16 MB).
(The CI 3100 is only available with 6 and 16 MB memory expansions)
The following points should be considered when choosing adequate memory capacity:
S 2 MB is equivalent to 40 memory units
S Archiving of operating data of a case controller are:
- UA 300 occupies 1,4 memory unit,
- UA 300 D occupies 1 memory unit,
- UA 300 E / UA 400 E occupies 2,3 memory unit,
- UA 300 L occupies 1 memory unit,
- UA 410 / UA 410 E occupies 2,5 memory unit,
S Archiving of operating data of a pack controller are:
- VS 300 occupies 2 memory unit,
- VS 3010 / VS 3010 BS occupies 2,5 memory unit,
- FS 3010 occupies 3 memory unit and
S Archiving of one case controller with up to 2 control zones according to the EU Directive occupies
- 2 memory units.
S The archiving of one wireless TS 30 W / TS 30 XW temperature sensor:
- occupies 0,2 memory units. The memory needed by the associated WR 300 / WR 400 receiver module
is negligibly small.
S Archiving of GLT 3010 occupies 1 memory unit