3. Generator
Bat. charge current limit(A): Maxi-
mum battery charge current from
the generator. The generator will
start charging according to the
‘Charge start Volt/SOC’ and stop
charging when the battery voltage or
SOC reaches the ‘Charge end
Volt/SOC’ value
.
Gen rated power(kW): The inverter
has a peak-shaving function. Users
can enable it and set up the Gen
peak-shaving power with this setting.
4. Discharge Settings
Operating Mode: Users can choose
‘Use SOC %’ or ‘Use Bat V” to control
the battery discharge state.
Discharge current limit(A): The maxi-
mum discharge current from the bat-
tery.
Discharge start power(W): The min-
imum value can be set to 50.
When the inverter detects the import power is higher than this value, the battery starts discharging; other-
wise, the battery will stay in standby.
On-grid Cut-off (%), Off-grid Cut off (%) / On-grid Cut-off(V), Off-grid Cut off(V): End of discharge SOC/Cut-
off voltage when the system is in an on-grid or off-grid situation, respectively.
Forced discharge: This setting will force the battery to discharge within the programmed period. In the pre-
set period, the inverter will discharge the battery at the power set by ‘Discharge power(kW)’ until battery
SOC or voltage reaches ’Stop discharge’ value.
5. Advanced Settings
Important!
The following settings may need to be adjusted by the installer after installation.
Please consult with your installer/distributor before making any changes to avoid conflicting settings
or damage to your system!