User Manual Chapter 3
GFK-1742F Jan 2020
Installing and Wiring the DSM314 89
Optically Isolated Enable Relay Output
Circuit
Identifier
Digital Servo
Axis 1, 2 Circuit
Function
Analog Servo
Axis 1-4 Circuit
Function
Aux Axis 2-4
Circuit Function
Signal Name
(X = A, B, C,
or D
Connector)
Faceplate
Pin
Auxiliary
Terminal
Board
Servo
Terminal
Board
ENBL
Servo MCON (+)
Servo MCON 0v
Drive Enable (+)
Drive Enable (-)
Drive Enable (+)
Drive Enable (-)
ENBL1_X
ENBL2_X
15
33
15
33
N/C
N/C
I/O Type: Optically Isolated Enable Relay Output
Circuit Type: Isolated AC Solid State Relay (SSR)
Output Current: 30 mA continuous, 50 mA for 10 ms
Output Voltage Drop: 1.0 v max at 10 mA
Note: This is a low current SSR output. The output is ON when the associated faceplate Axis Enabled
LED is illuminated. This occurs when:
The servo is enabled
A Force Digital Servo Velocity %AQ Cmd is used (Axis 1, 2) A Force Analog Output %AQ Cmd is
used