I/O Type: 24v DC Optically Isolated Output
Circuit Type: Isolated Solid-State Relay (SSR)
Output Current: 125 mA continuous, 500 mA for 10 ms (resistive or
inductive)
Output Voltage Drop: 1.0 v max at 0.125 amps
Note: Output is protected by a 30v transzorb and a 0.2-amp Polyswitch. If a short circuit occurs, the
output will automatically switch to a high impedance state until the load is removed. The load
should not be reapplied for 60 seconds. This is a dc output and it will appear to be always ON if
connections to it are reversed.