User Manual Appendix A
GFK-1742F Jan 2020
Error Reporting 366
Table 79: DSM314 Error Codes
Scaled data too big,
maximum value in range used
Check DSM axis configuration in HWCFG
Home Position > Positive EOT,
Positive EOT used
Check DSM axis configuration in HWCFG
Home Position < Negative
EOT, Negative EOT used
Check DSM axis configuration in HWCFG
Tuning parameter row 1
invalid; data ignored
Check DSM tuning configuration in HWCFG
Advanced Tab Row 1
Tuning parameter row 2
invalid; data ignored
Check DSM tuning configuration in HWCFG
Advanced Tab Row 2
Tuning parameter row 3-16
invalid; data ignored
Check DSM tuning configuration in HWCFG
Advanced Tab One or more than one
parameter in row 3-16 is invalid
Output written by Local Logic
is not configured for Local
Logic control
A Local Logic block name is specified in the
configuration and the Hardware
Configuration (Output Bits Tab) for the
module does not have the required output
configured for Local Logic control.
CTL bit written by Local Logic
is not configured for Local
Logic control
A Local Logic block name is specified in the
configuration and the Hardware
Configuration (CTL Bits Tab) for the module
does not have the required CTL bit
configured for Local Logic control.
Configuration Parameter Errors
Software End of Travel is enabled in
configuration and the High or Low Software
End of Travel values are set outside the High
or Low Count Limits. Configuration should
be changed by either disabling the Software
End of Travel or setting the End of Travel
values within the Count Limits.
(Aux only) Scaled rotary EOT
count modulus is not an
integer
Check DSM axis configuration in HWCFG.
Scaled rotary Hi/Lo limit
count modulus is not an
integer
Check DSM axis configuration in HWCFG.
Unsupported AQ command
mode
The AQ commands that configure Torque
Mode variables are not available in Analog
Velocity Mode.