Section 11 User Access
11 – 3
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Verify Password
This entry box is to verify the operator’s password.
The password can be entered by touching the “Verify
Password” entry box and entering the password via the
pop-up keyboard.
Security Level
This drop-down list allows selection of security level for
the account being added or modied. Only levels that
are equal to or less than the operator’s own security level
will be shown.
Add / Update
Pressing this button will initiate the creation or modica-
tion of the specied account.
Delete
Pressing this button will delete the specied account.
Screen Security Levels
The following table lists all screen and their base security
levels, see Table 11-1. Most screens have more than
one security level. The base security level gives the user
access to the setpoints that can change the performance
of the compressor. The secondary security level is
typically level 3 and is reserved for those setpoints that
require a high level of care and knowledge of the system
to make changes safely without damaging the system.
Table 11-1. Security Access Levels
Security Access Levels
Page User Level Note
Event List Level 0 View
Input/Output States Level 0 View/create freeze screen
Trend Chart Level 0 View/operate
Help Level 0 -
Alarms & Trips Level 1 Level 3 or Level 4 required for constraints
Compressor Scheduling Level 1 -
Compressor Control Level 1 Level 3 required for constraints
Maintenance Level 1 -
Data Backup Level 1 Level 3 required to upload data
Instrument Calibration Level 2 -
Service Options Level 2 -
Conguration Level 2 Level 3 required for page 5 to page 8
Timers Level 2 Level 3 or Level 4 required for constraints
VNC Account Level 3 -
Compressor Sequencing Level 2 -
Auxiliary I/O Level 2 -
Condenser Control Level 1 Level 3 required for constraints