Section 10 Input / Output States Screen
10 – 1
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Overview
This screen displays “Live Data” of all the Analog Inputs /
Outputs, Digital Inputs / Outputs, Virtual Analog Inputs,
Virtual Digital Inputs, Analog Result Variable and Digital
Result Variables being monitored. There are Six pages of
Inputs / Outputs (I/O) available for viewing, see Figures
10-1, 10-2, 10-3, 10-4, 10-5 & 10-6.
This screen also takes a snapshot of all the I/O points
when the operator presses on “Freeze Data” button or if
the compressor experiences a trip condition. The Freeze
page displays the title that indicates whether the Freeze
data is saved due to trip condition or “Freeze Data” but-
ton was pressed by the operator, see Figures 10-7 & 10-
8. Latest Freeze data is shown in Freeze 1 tab. Up to ve
Freeze pages can be saved. The oldest Freeze page will
be removed when more than ve Freeze events occur.
These freeze events can be downloaded to a USB drive
through Data Backup screen.
Figure 10-1. Input/Output States Screen Page 1 - Live I/O Data